Mor Electric HeatingQuestions? 616-784-1121 Email Us8:00am-5:00pm M-F (Eastern Time)Distributor for 75 Manufacturers with Over 1,500 SKUs Typically in Stock for Same Day Shipping
Pipe Temperature Maintenance, Self-Regulating, Cut-to-Length. For Commercial Applications
Reduces maintenance requirements by eliminating return piping, pumps, check valves and pressure balancing valves found in recirculating systems
Designed to maintain nominal domestic water temperatures of 105 °F, 115 °F, 125 °F and 140 °F
Self-regulating heater cable is a parallel circuit electric heater strip
An irradiation cross-linked conductive polymer core material is extruded over the multi-stranded, tin-plated, 16-gauge copper bus wires
The conductive core material increases or decreases its heat output in response to temperature changes
Two jackets provide extra dielectric strength, moisture resistance, and protection from impact and abrasion damage. The inner thermoplastic jacket is extruded over and bonded to the core material
A thermoplastic elastomer over jacket is then extruded over the inner jacket
A stranded tinned copper metal braid is supplied on all heaters. A color-coded modified polyolefin over jacket is supplied for positive identification during installation
Specifications
Certifications
UL Listed for domestic hot water temperature maintenance and meet all requirements of IEEE Standard 515.1, Recommended Practice for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Commercial Applications